MIM with IO-Link & Stainless Steel

  • Type:Magnetic Inductive Flowmeter
  • Medium:Conductive Liquid
  • Flow Rate : 0.01 – 1 l/min … 1.5 – 650 l/min
  • Nominal Meter Size: G ¼, G ½, G ¾, G 1, G 2, 2″ NPT
  • Accuracy:±(0.8% of reading + 0.5% of FS)
  • Max. Temperature:-40…140℃
  • Max. Pressure:16bar
  • Warranty:1 year warranty

The MIM electromagnetic flowmeter measures and monitors small to medium sized flow of conductive liquids in pipes. According to Faraday’s Law of magnetic induction, a voltage is induced in a conductor moving through a magnetic field. The electrically conductive measured media acts as the conductor. The voltage induced in the measured media is proportional to the flow velocity and is therefore a value for the volumetric flow. The induced voltage is detected by two sensing electrodes which are in contact with the measuring media and sent to an integrated amplifier. The flow rate will be calculated based on the cross sectional area of the pipe. The measurement does not depend on the process liquid and its properties such as density, viscosity and temperature. The two outputs can be independently set to switch, or provide an analog or frequency output.

Features & Benefits

  • Rugged Stainless Steel Construction
  • Flow and Temperature Measurement
  • Switching, Transmitting, and Batching Functions
  • Batching Function with External Control Input
  • Bi-directional Flow Measurement
  • Colored, Multi-parameter, Configurable TFT Display, Rotatable in 90° Increments
  • Intuitive Setup Menu via 4 Optical Touch Keys
  • 2 Configurable Outputs (Pulse/Frequency/Alarm/Analog Output)
  • Grand and Resettable Totalizer

Technical Datasheet

Ranges: 0.01 – 1 l/min … 1.5 – 650 l/min
Media: Conductive Liquids
Min. Conductivity:  ≥ 20 µS/cm

Native Fittings: G 1/4…G 2, or 1/2″ NPT…2″ NPT

Optional Fitting Kits: 1/4″…1″ NPT (Male or Female), 1″ or 2″ Tri-Clamp

Max. Pressure: 16bar

Accuracy 1): ≤ ± (0.8% of Reading + 0.5% of Full Scale)

Repeatability: ± 0.2% of Full Scale

Response Time Flow t90
Alarm / Pulse /
Frequency Output: < 100 ms

Analog Output:< 1 s

Temperature Measurement Sensor: PT1000 ( Option )

Programming 2):  Via 4 Optical Touch Fields, can be used with Gloves

Inlet / Outlet: 3 x Upstream, 2 x Downstream

Housing: 316L Stainless Steel, PMMA Display Screen

Insulation Parts: PEEK

Supply Voltage: 19 – 30 VDC, Internal Power

Consumption max. : 200 mA

 

 

1) Reference Cond.: Media: 60…85 °F, 1 cSt, 500 µS/cm, 15 PSI, Ambient: 60…85°F

2) Limited functionality with black rubber gloves